WARNING
CALL YOUR ELECTRICIAN
Your building may have one of these Federal Pacific Circuit Breakers which need to be replaced, or field modified:
NEJ/HEJ NFJ/HFJ NEG/HEG NEF NP
Under certain conditions these breakers could cause personal injury or property damage.
FPE circuit breakers are most likely to be found in enclosures marked
FPE, However, they may also be found in some enclosures made by other manufacturers, such as: Zinsco, Sylvania, Frank Adam Electric Co.
THEY WILL NOT BE FOUND IN ENCLOSURES MARKED GE,
WESTINGHOUSE, ITE, SQUARE I), AND CUTLER-HAMMER.
Because of the difficulty in identifying these devices, have your on-site electrician or facility engineer review the following chart to determine if you have any of these FPE Breakers.
Identification chart of breakers involved in corrective actions
BREAKER
TYPE
AMPERE
RANGE POLES
VOLTS A.C.
RATING MAX.
TYPE OF
FACILITY
CORRECTIVE ACTION
REQUIRED
NEJ/HEJ 70-225 2 & 3 240 Light Industrial REPLACE BREAKERS
NFJ/HFJ 70-225 2& 3 600 Industrial REPLACE BREAKERS
INSTALLED ON ELECTRICAL
SYSTEMS ABOVE 550 VOLTS
NEG/HEG 30-100 2 & 3 600 Heavy Industrial MODIFY BREAKERS INSTALLED
ON 480 VOLTS OR ABOVE.
MODIFY BREAKERS INSTALLED
IN FPE ENCLOSURES 1100T.
NEF 40-100 2 & 3 480 600
Commercial and
Industrial
REPLACE BREAKERS
NP 600-2500 2 & 3 600 Large Electrical
Distribution
Systems
REPLACE BREAKERS
INSTALLED ON ELECTRICAL
SYSTEMS WITH AVAILABLE
FAULT CURRENTS ABOVE 85,000 AMPERES AT 240 VOLTS
OR 50,000 AMPERES AT480 AND 600 VOLTS OR WHERE
ROUTINELY USED AS A SWITCH
This is part of a program voluntarily initiated by Federal Pacific. The Consumer Product
Safety Commission has been notified. Lab tests have indicated that these Circuit Breakers could cause personal injury or property damage. Federal Pacific will respond as soon as possible by phone or mail. Allow 6 weeks for this preliminary contact.
If your electrician finds you have these FPE breakers in service, or if he is uncertain, please call, toll free: 800-526-3962 (In N.J.: call 800-942-7773.)
YOUR SAFETY IS OUR CONCERN.
Yes. We have
Please have an FPE engineer contact us.
Name
Title breakers in use.
Company
Address _
Phone
FRrE
PRODUCT RECOVERY CENTER
FEDERAL PACIFIC
ELECTRIC COMPANY
P0 BOX 1800, Somerville, NJ 08876 (201) 526-1330 272-R-1
September 15, 1981 Write 292 on Reader Service Card 39